Varmra · Guide
Zones in an energy balance
Varmra can split a building into zones, each with its own temperature, heating, ventilation and use, and calculate them together hour by hour to BBR.
Why zones
A simple energy balance treats a building as one room at one temperature, heated by one system and aired by one unit. Many buildings are not like that:
Different temperatures
A garage kept at 15 °C, a store left cold, a heated house beside them.
Different heating
Radiators in one flat, floor heating in the other; two heat pumps.
Ventilation in part
Heat recovery (FTX) for the house, plain exhaust for a guest house.
Mixed and large buildings
Dwellings and premises in one building, schools, many storeys.
Boverket's BEN asks for the same: its general advice is to divide a building into zones when its spaces differ in indoor temperature, in the systems that heat, cool or air them, or in internal loads.
What a zone is
In Varmra, a zone is a set of rooms that share four things:
- a set point, or none (then it floats);
- a heating circuit: a heat plant and its emitters;
- a ventilation unit, or none;
- a use, which brings BEN's standard values for people, hot water, lighting, equipment and hours.
Each envelope part (wall, roof, floor, window, door) belongs to the zone its rooms are in. The walls and floors between zones are couplings: heat passes through them, U times A times the temperature difference, and what leaves one zone arrives in the other.
Storeys and zones are independent: a zone may span storeys, and a storey may hold many zones.
How zones are calculated
Varmra's energy balance is the hourly model of ISO 13790, annex C (the simple hourly 5R1C network), run over the 8,760 hours of a normal year for the building's location. With zones, every zone gets its own network, and the zones are coupled between their air temperatures.
- Every hour, all zones are solved together until no zone's temperature moves by more than 0.00001 K. A house and a garage need about three passes.
- Each zone is heated and cooled to its own set points, within its own heating power.
- A zone with no set point is not heated: its temperature follows from its losses, its gains and its neighbours.
- A project with no zones is calculated as one zone, exactly as before. One zone that is the whole building gives the same results as the single-zone model.
Unheated spaces float
A garage, a store, an attic or a crawl space without heating is a zone with no set point. It is not left out of the calculation, and it is not assumed to be at the indoor temperature either: it finds its own temperature, hour by hour, from the heat it gets from its heated neighbours, the sun and its own losses outdoors.
3.1 °C
the free garage's January mean
910 kWh a year
from the house into the free garage, through the one wall
+2,036 kWh a year
to keep the garage at 15 °C: outside Atemp, still in the building's energy use
In a single-zone model the same garage is either left out, or its walls, roof and slab are counted as if heated to the house's temperature. Neither is what happens. With zones, the house's loss to the garage, the garage's own heat and the garage's temperature are all computed.
BBR with zones
Varmra applies the rules of BBR chapter 9 zone by zone, and shows how each one was worked out.
| Rule | With zones |
|---|---|
| Atemp | The floor area of the zones meant to be heated above 10 °C, inside the envelope. A garage never counts in Atemp, whatever its temperature. A crawl space is inside the envelope but out of Atemp. |
| Energy use | Heat delivered to every zone, the garage's too, plus cooling, hot water and building services, per energy carrier. |
| Aom and Um | The parts bounding heated zones. A wall from the house to an unheated zone counts, with a reduction factor (b-factor, EN ISO 13789) for the unheated space behind it; the garage's own outer walls do not. |
| Mixed buildings | Dwellings and premises in one building: the limits on Um, primary energy (EPpet) and installed power are weighted by Atemp. |
limit, mixed building = (A_dwellings · L_dwellings + A_premises · L_premises) / Atemp
Calling a garage a hobby room changes nothing. A garage is out of Atemp because it is a garage, and the heat it takes counts in the energy use either way. A real hobby room heated above 10 °C is in Atemp like any other room. The honest choice is a garage outside the heated envelope, kept at 10 °C or less, and the zone model shows what that costs.
Uses and their standard values
A zone's use brings the standard user inputs from BEN (BFS 2016:12 with amendments), tables 2:1 to 2:7. Each value shows in the zone and can be changed, like the project's own standard values.
| Use | Set point | Standard values |
|---|---|---|
| Dwelling, house | 21 °C | hot water 20 kWh/m², household electricity 30 kWh/m² (70 % as heat), 80 W a person (table 2:1) |
| Dwelling, flats | 21 °C | hot water 25 kWh/m², household electricity 30 kWh/m² (70 % as heat); 22 °C in elderly care (table 2:2) |
| Office | 21 °C | hot water 2 kWh/m², activity energy 50 kWh/m², 20 m² a person (table 2:4) |
| Preschool | 22 °C | lighting 4 and equipment 2 W/m², 15 m² a person (table 2:5) |
| School, classrooms | 22 °C | lighting 5 and equipment 5 W/m², 15 m² a person (table 2:6) |
| University | 22 / 20 °C | in use / outside hours, 15 m² a person (table 2:7) |
| Store, technical | 18 °C | premises with no people and no activity energy |
| Garage, crawl space, attic | set or free | never in Atemp; a garage's heat still counts |
Premises run on their use's hours: people, lighting and equipment follow BEN's hours a day, days a week and weeks a year, so a school is empty at night, at weekends and in summer.
Heating and ventilation per zone
With zones, systems are described as they are built: a list of what is there, which the zones point to.
Heat plants
Heat pumps by model or SCOP, district heating, boilers, direct electric; which one makes the hot water.
Heating circuits
Radiators, floor heating or supply-air coils, each at its supply and return temperature.
Ventilation units
Exhaust (F), supply and exhaust (FT), heat recovery (FTX), exhaust air heat pump; each with its fans and hours.
Zones point to them
A zone takes a plant's circuit and a unit. FTX in only part of a house is two units.
- A heat pump's SCOP follows its circuits. It is taken at the supply temperature of the circuits it serves, weighted by their heat. In the two-flat example above, the flat with floor heating at 35 °C gets a better SCOP than the flat with radiators at 45 °C.
- An exhaust air heat pump is limited by the air of its own unit, not the whole building's.
- Solar power and batteries stay with the building as a whole.
The system diagram (P&ID) on the Project step draws a project with zones in the same way as one without: each plant with its water heater and shunt group, the zones it heats beside it in their colours, each ventilation unit under the plant whose heat pump it feeds, and the hour's power on each line. A click on a zone goes to where it is set.
Floor heating's loss downward
A heated floor is warmer than the room above it, so it loses more heat downward than the same floor under radiators. Varmra computes this from EN 1264-2 in projects with zones:
Δθ = q · (1/10.8 + R_λ,B)
q heat output of the floor, W/m²
10.8 heat transfer from floor to room, W/m²K
R_λ,B the floor covering's resistance, m²K/W (0.10 typical)
The floor below loses U · Δθ more in every heating hour. At 20 W/m² the heated layer is about 3.9 K above the room:
| Floor below | U, W/m²K | Extra loss |
|---|---|---|
| Insulated slab on ground | 0.12 | about 2 % of the floor's output |
| Uninsulated timber floor over a crawl space | about 0.75 | about 15 % |
Into a heated or floating zone below, the heat is not lost: the coupled model hands it to that zone. Radiators add no such term.
Making zones in Varmra
Zones live on the Building envelope step. With a model imported from EikHub, Stomra or an OpenEik folder, Varmra knows the rooms, which flat or unit each belongs to, and which walls and floors lie between them.
- Propose zones. Choose Make zones from the model's rooms. Varmra puts each flat or unit the rooms name, a garage, the unheated rooms and each crawl space in a zone of its own, and the rest in one zone. Nothing becomes zones on its own: you start it.
- Adjust them. Rename zones, add one with New zone, or move a room to another zone with its move to choice. The room's walls, floors and windows follow it, and so do the couplings.
- Set each zone. Its use, its set point or no heating, its heating (plant, emitter and supply temperature) and its ventilation (unit and outdoor air).
- Describe the systems. On the Systems step, add the heat plants and ventilation units; each shows which zones it serves.
- Read the results. Each zone shows its year: heat, mean, lowest and highest temperature, heat to or from other zones and, with floor heating, the loss downward.
Without a model, choose Split by hand: you type each zone's floor area and add the walls and floors between zones in a small form (the two zones, area, U, floor or wall). Back to one zone returns to a single-zone calculation.
Once a project has zones, the Atemp field is the zones' sum, and the envelope table gets a Zone column. Each zone has a colour, used the same way in the panel, the diagram and the 3D view.
In the 3D review, the Zones lens colours each envelope part by its zone and labels each zone with its temperature at the hour you pick. Unheated zones show in grey at the temperature they float to. See Reviewing a building in 3D.
Results, report and connector
Results
A table per zone (area, in Atemp or not, set point, heat, peak, temperatures), each plant's heat, hot water and supply temperature, and in a mixed building the weighting of the limits.
Report
A chapter Zones (Zoner in Swedish) after the building envelope: zones, plants, and every wall and floor between zones with its year's heat, with BBR and BEN as the sources.
Connector
An assistant sets zones by the model's rooms with set_zones (a proposal or a dry run first, if you like) and reads each zone, plant and coupling from calculate.
Terms
| Zone | Rooms sharing a set point, a heating circuit, a ventilation unit and a use. |
|---|---|
| Coupling | A wall or floor between two zones; heat flows through it as U · A · (θ1 − θ2). |
| Floating zone | A zone without heating, whose temperature follows from its surroundings. |
| Atemp | The floor area of spaces meant to be heated above 10 °C, to the inside of the envelope (BBR 9:12). |
| Aom, Um | The area of the parts bounding the heated spaces, and their mean U-value including thermal bridges. |
| EPpet | The building's primary energy number, kWh/m² Atemp a year, against BBR's limit. |
| 5R1C | ISO 13790's hourly network of five conductances and one heat capacity per zone. |